OIL & GAS EQUIPMENT  |  Updated November 2026  |  8 min read
WHAT YOU’LL LEARN IN THIS GUIDE
  • What a flame arrestor actually does, and the limits of what it can stop
  • Where arrestors belong on flare, vapor combustor and tank vent installations
  • End-of-line vs in-line, and deflagration vs detonation arrestors
  • The specification points to confirm: gas group, burn duration, pressure drop and test standard
  • Common installation mistakes that turn a safety device into a process problem
  • An inspection and maintenance routine that keeps the element clear

A flame arrestor is one of the least glamorous parts on a combustion system, and one of the few that can decide whether a small ignition event stays small. When a flame travels backward through a vent line, it can reach a tank, a compressor suction or a gathering header holding a flammable mixture. The arrestor sits in that path and stops the flame from getting through. This guide explains how the device works, where it is used around flares and vapor combustors, and what to check when you specify, install and maintain one.

Hero Process Solutions, based in Kellyville, Oklahoma with field operations in Midland, Texas, keeps flame arrestors in stock as part of its aftermarket parts program, alongside pilot assemblies, ignition and burner management systems, and blowers. The guidance below reflects the questions operators ask when a replacement is needed or a retrofit is being planned.

DIRECT ANSWER: What Does a Flame Arrestor Do?

A flame arrestor is a passive device that lets gas flow through while stopping a flame from travelling back through the line. Its element is built from many narrow passages. As the flame enters them, the metal absorbs enough heat that the flame is quenched. It has no moving parts and needs no power, but it only works when it is the right type, the right gas group and the right size for the service, and when its element is clean.

How a Flame Arrestor Works

Every flammable gas has a maximum experimental safe gap (MESG). This is the narrowest gap a flame can still pass through. Make the passage smaller than that gap and the surrounding metal pulls heat out of the flame faster than combustion can replace it, so the flame goes out. A flame arrestor element is a bundle of such passages, built as crimped metal ribbon, parallel plates or expanded metal. The tighter the gap, the harder the gas group it can handle, and the more resistance it adds to flow.

It helps to be clear about what an arrestor is not. It is not a flame monitor, it does not extinguish a fire that is burning at the outlet for a long time, and it does not replace a properly designed ignition and pilot system. It protects the upstream side of a line from a flame that has already started on the downstream side.

Where Flame Arrestors Sit on Flare and Combustor Systems

On upstream and midstream sites, arrestors usually appear in three places:

  • Tank vapor lines feeding a combustor. Where storage tank vapors are routed to a vapor combustor unit, an arrestor in the supply line keeps a flashback from reaching the tanks.
  • Vent and collection headers. Where several vent sources join before a combustion device, an arrestor limits how far a flame can travel into the collection system.
  • Fuel and air paths on enclosed combustion equipment. Where a mixture of fuel and air exists upstream of a burner, a flashback path can exist, and an arrestor is one of the barriers used to close it.

Open flare headers are a different case. Because heavy or sticky streams can foul a fine-gap element, many flare headers rely on continuous purge gas and a seal to keep air out, rather than an arrestor in the main header. Our guide to flare purge gas and molecular seal design covers that approach in detail.

Gray ignition and burner control panels mounted on a galvanized frame beside a pipe rack at an oil and gas site
Control panels for ignition and burner management sit alongside the safety devices that protect the vent lines.

Types of Flame Arrestors

End-of-line vs in-line

An end-of-line arrestor mounts at the open end of a vent pipe, so a flame outside the pipe cannot enter it. This is the common choice on tank breather and vent outlets. An in-line arrestor sits in the middle of a pipe run, with piping on both sides, and is used where the flame could enter from either direction or travel along the line toward a protected vessel.

Deflagration vs detonation

A deflagration is a flame front moving below the speed of sound. A detonation is a shock-driven flame front moving faster than the speed of sound, and it brings a much higher pressure load. In a long straight pipe, a deflagration can accelerate and become a detonation as it travels. That is why the arrestor type depends on how far it sits from the likely ignition source. A deflagration arrestor suits short runs. A detonation arrestor is built with a stronger housing and element, and is used where the run is long enough for a flame to build speed.

Dry element vs liquid seal

Most arrestors are dry-element devices. A liquid-seal (hydraulic) arrestor forces the gas to pass through a column of liquid, which breaks the flame path. It can handle some dirty services well, but it needs liquid level control and freeze protection, so it carries more upkeep.

Gas group (IEC) MESG Typical gases
IIA0.90 mm or moreMethane, propane, most natural gas streams
IIBAbove 0.50 mm, below 0.90 mmEthylene and similar streams
IIC0.50 mm or lessHydrogen, acetylene

Gas groups follow the IEC 60079-20-1 classification. Confirm the group for your own gas composition before you specify an element.

What to Confirm When You Specify One

Use this list to build the datasheet request, whether you are replacing a unit or adding one to a new skid.

  1. Gas group. Match the element to the most demanding gas in the stream, including any hydrogen content. A natural gas stream with a hydrogen-rich side stream is not a group IIA problem anymore.
  2. Burn duration. Ask whether a flame could sit at the outlet for seconds or for hours. An arrestor rated for short-time burning can be overwhelmed by a sustained flame. Endurance-burn units are tested for that case and often add a temperature sensor so the site can respond.
  3. Test standard and approval. Look for performance testing to a recognized standard such as ISO 16852 and for the approvals your site or insurer requires. An untested element is a guess.
  4. Pressure drop and flow. The element restricts flow. Size for the real peak vent rate, and check the clean and fouled pressure drop against what the protected equipment can tolerate.
  5. Operating temperature and pressure. Hot vent gas changes the quenching margin, and some arrestors are only approved up to a stated temperature.
  6. Materials and connections. Housing and element material must suit the gas, including any H2S, and the connection must match the line.
  7. Fouling tendency. Wax, polymer, salt and liquid carryover all clog fine passages. If the stream carries any of these, say so up front.

Installation Mistakes We See in the Field

  • Back pressure on a low-pressure tank. Atmospheric tanks have very small pressure limits. A fouled arrestor in the vent path can push the tank above its rating before anyone notices.
  • Wrong distance from the ignition source. An in-line deflagration unit placed far from the likely ignition point may see a flame that has already accelerated.
  • Insulating over the housing or sensor. Heat has to leave the element for it to quench a flame, and a temperature sensor has to see the real surface.
  • Using an arrestor to fix a pilot problem. An arrestor does not keep a pilot lit. If the pilot drops out, the cause sits in the pilot or burner control system, and our write-up on spark vs pilot ignition is the better starting point.
  • No drain or condensate plan. Liquid that collects ahead of the element blocks flow and can freeze in winter.
Flare pilot and ignition hardware with monitoring equipment mounted along a cream-colored flare stack under a clear blue sky
Pilot, ignition and monitoring hardware on a field flare stack. Each of these parts needs a planned inspection routine.

Inspection and Maintenance

A flame arrestor that has never been opened is a device nobody can vouch for. A practical routine looks like this:

  1. Record a baseline. Note the clean-element pressure drop at a known flow when the unit is new or freshly cleaned.
  2. Watch the differential. A pressure gauge across the element shows fouling before it becomes a process problem. A rising trend is the signal to schedule cleaning.
  3. Set the interval by service, not by habit. Clean gas may need a yearly look. A stream with wax or condensate may need monthly checks. Let the first few inspections show what is real.
  4. Handle the element gently. Crimped ribbon is easy to bend. A dented or distorted element changes the gap and should be replaced, not straightened.
  5. Check seals, gaskets and the housing. A leaking joint is a path around the element, and corrosion thins the housing.
  6. Keep a spare element. A fouled unit should come out and a clean one go in, so the line stays protected while the first one is cleaned.
  7. Log every inspection. Date, pressure drop, findings and action. Auditors and insurers ask for it.

Arrestor checks fit naturally into the same visit as pilot, igniter and flame-monitoring inspections. The EPA flare requirements in 40 CFR 60.18 call for the presence of a pilot flame to be monitored, and the newer Subpart OOOOb rules raise the expectations on combustion devices at covered oil and gas facilities. For pilot system design practice, see the API 537 standard, and for current federal rule status see the EPA oil and natural gas actions page. Our guide to flare tip erosion and replacement is a useful companion for planning one combined inspection scope.

When to Repair, Replace or Retrofit

Replace an arrestor when the element is damaged, when cleaning no longer returns the pressure drop to baseline, or when the gas composition has changed and the original gas group no longer fits. Plan a retrofit when the arrestor is only one of several aging parts around the combustor, such as the pilot, the ignition system or the controls. Hero supports its own equipment, legacy Hero Flare and Tri-Point Oil and Gas units, and equipment from other manufacturers, with stocked parts and field services including inspections and retrofits. If you also manage a rental or temporary installation, ask about arrestor needs when you arrange the rental.

NEED A REPLACEMENT OR A SECOND OPINION?

Send us the line size, gas composition, operating pressure and temperature, and the make and model of the unit you have now. We will confirm what is in stock and what the service needs. Contact Hero Process Solutions or call (918) 941-2166.

Frequently Asked Questions

Is a flame arrestor the same as a flame trap?

The terms are used interchangeably in many plants. Both describe a passive device with narrow passages that quenches a flame. Specifications and standards use the term flame arrester or flame arrestor, so use that on a datasheet or purchase order.

Do I need a detonation arrestor or is a deflagration arrestor enough?

It depends on how far the arrestor sits from the possible ignition point and how long the straight pipe run is. Short runs usually point to a deflagration unit. Long runs, or lines that can hold a flammable mixture over a large length, call for detonation-rated protection. Have the unit’s tested pipe length and approval confirmed before you buy.

How often should a flame arrestor be inspected?

There is no single interval. Clean gas service can run a long time between checks, while wax, condensate or salt can foul an element within weeks. Track the pressure drop across the element and tighten the interval if the trend rises.

Can I clean a clogged flame arrestor element?

Often yes, if the element is undamaged. Use a method the manufacturer allows, avoid anything that bends the ribbon or plates, and confirm the pressure drop returns to the baseline. If it does not, replace the element.

Does Hero Process Solutions stock flame arrestors?

Yes. Flame arrestors are part of the stocked aftermarket parts list, along with pilot assemblies, ignition and burner management systems, blowers, pumps and actuators. Hero supports its own equipment, legacy Hero Flare and Tri-Point Oil and Gas equipment, and units from other manufacturers. Contact the team for availability on a specific size.